Heat sensing for addressable lines on the TTE protocol, aimed at catching a fire early; it plugs into the B124 base. Either a fixed temperature or a rate of rise can trigger it, and the panel switches its class between A1R, A2S and BS. Low-profile housing, LED seen all round, EN 54-5 certified. Power 15-32 V DC (27 V nominal), standby below 180 uA, alarm 6.5 mA. IP30, -10 to +65 C, 103 x 42 mm with base, 110 g. The variant with an isolator inside the detector is SensoIRIS T110 IS.